Medical Facilities

Case Study

EdgeCool components

Protecting Mission-Critical Healthcare Technology Without the Complexity of Traditional Cooling

How Retina Consultants of Southern Colorado Solved Server Room Overheating with EdgeCool

Retina Consultants of Southern Colorado relies on networking and IT infrastructure to support daily clinical operations, advanced retinal diagnostics, and surgical procedures.

But inside a compact 6′ × 8′ server room, the heat generated by critical IT equipment was exceeding what the building’s HVAC system could effectively manage.

When the building HVAC system reduced operation during evenings, weekends, and other periods, temperatures inside the server room began to rise. Staff were forced to leave the server room door open and use fans to help cool the equipment.

While this brought temperatures down to approximately 80°F, it introduced new concerns around equipment reliability and physical security and raised the possibility of disruptions to scheduled surgeries.

The practice needed a permanent cooling solution that could be installed quickly, protect critical infrastructure, and avoid major modifications to the facility

 

EdgeCool components

Challenge

A Small Room Supporting Critical Infrastructure

Although the server room was relatively compact, it housed both a network cabinet and a partially populated two-post rack containing critical infrastructure. The heat generated by this equipment consistently exceeded what the surrounding building HVAC system could effectively manage.

Infrastructure Constraints

The room’s IT equipment created a concentrated heat load that the building HVAC system wasn’t designed to address.

Security Risks

Leaving the server room door open to maintain acceptable temperatures exposed critical infrastructure to unauthorized access and created additional operational concerns for facility and IT personnel.

Healthcare Facility Considerations

Any cooling upgrade needed to minimize disruption to daily operations while providing long-term reliability. Extended construction timelines, permit requirements, and invasive building modifications were undesirable in an active healthcare environment.

Limited Time for Implementation

The practice needed a solution that could be deployed quickly rather than waiting months for engineering reviews, permits, and contractor scheduling.

EdgeCool components

Solution: Targeted Cooling. Minimal Disruption. No Major Facility Modifications.

Retina Consultants selected the EdgeCool 5 Series In-Rack Cooling System to provide targeted cooling precisely where it was needed most.

Unlike conventional room-based air conditioning, EdgeCool delivers cooling directly to the IT equipment while operating from a standard 115V electrical connection.

The system reduced the inlet temperature to the IT equipment to the low 60s, providing the dedicated cooling the critical infrastructure required.

Installation was completed by Tolin Mechanical in approximately four hours with two technicians.

A

Designed Around the Existing Environment

One of the advantages of the EdgeCool installation was its ability to work with the facility’s existing infrastructure rather than requiring significant building modifications.

A

Rack-Mounted Condenser Integration

The server cabinet had sufficient available rack space, allowing the condenser section to be installed directly within the existing rack environment. This eliminated the need to consume additional floor space.

A

Simplified Air Management

Warm exhaust air was ducted directly into the building’s drop ceiling. This avoided the need for rooftop equipment and extensive ductwork modifications.

A

Straightforward Condensate Removal

Condensate was routed to a neighboring janitorial closet using a condensate pump, avoiding costly plumbing alterations.

A

No Electrical Upgrades Required

An unused dedicated 115V / 20A outlet was already available inside the server room. As a result, the installation required no new circuits and no electrician.

“In a healthcare setting, if our servers go down, it’s not just an inconvenience, it can delay patient care, from pulling up records to running diagnostic equipment. The temps in our server room were regularly above 80 degrees, and we were worried about the long term wear on our server and network equipment.”

– Shenandoah Bower, Retina Consultants

“The difference with EdgeCool was immediate. Temperatures in the server room dropped and have stayed consistent, even during peak loads and summer months.”

– Adam Baart, Colorado Hi Tech Solutions

EdgeCool brings “best value” in server-cooling for any environment. Get efficiency that pays you back in dollars saved. Let our EdgeCool technical expert spec a system for your environment.

Get a Quote

Product Specifications

UNIT TYPEEvaporator
EVAPORATOR
Condenser
CONDENSER
Model Number (sold separately)A5F5
Electronic ControlProgrammable
Electrical Charateristics
Voltage Requirements (60 Hz)1 Phase, 115 V
Total Power Consumption1.5 kW
NEMA Plug Configuration5-20P
Cooling Capacity and Power Consumption
Evaporator: 95°F @ 32% RH / Condenser: 81°F
Total Cooling Capacity15,400 Btu/h
4.5 kW
Sensible Cooling Capacity13,600 Btu/h
4.0 kW
Power Consumption1.5 kW
Refrigerant
TypeR410-A
Factory Charge Amount1.65 lb
Operating Conditions (Min-Max)65°F @ 50% RH - 113°F @ 30% RH
Max Airflow520/340/210 CFM (high/mid/low)765 CFM (1 speed)
Enclosure Dimensions17 x 33 x 13 in (8U Rack Space)17 x 34 x 16 in (9U Rack Space)
Max. Sound Level68/60/49 dB(A) (high/mid/low)70/72dB(A) (with duct/without duct)
Net Weight57 lb (26 kg)108 lb (49 kg)

Specifications subject to change without notice.

Evaporator Accessories

NO.PART NAMEDESCRIPTIONPART NUMBER
1Evaporator Rack Mount KitRackmounts Evaporator unit inside standard 19-in. Electronics Industries Association (EIA) rack. Includes, stays, brackets and bolts. (Does not include bolts and nuts to connect to vertical mounting rails)484009-1560

Condenser Accessories

NO.PART NAMEDESCRIPTIONPART NUMBER
2Condenser Rack Mount Kit - InternalRackmounts Condenser unit inside standard 19-in. Electronics Industries Association (EIA) rack. Includes, stays, brackets, screws, nuts and bolts. (Does not include bolts and nuts to connect to vertical mounting rails)484009-1580
3Condenser Rack Mount Kit - ExternalRackmounts Condenser unit on top of standard 19-in. Electronics Industries Association (EIA) rack. Includes, stays, brackets, screws, nuts and bolts. (Does not include bolts to connect to rack top panel)484009-1570
4Condenser Mount Rails - External & InternalRackmount adapter rails for deep racks, used with accessory No. 2 or 3484009-1630
5Air Plenum KitPlenum for return air to Condenser. Includes 12-in duct clamp.484009-1590
6Self-Supported Duct12-in diameter white, plastic duct that extends from 6.5 to 10-ft in length. (Includes clamp)LA481744-0410
7Flexible Air Duct12-in diameter wire-reinforced, accordion-style duct in 10-ft length for Condenser air exhaust. (Includes clamp)LAY45771-0060
8Celling Tile, 12-in hole, plastic24-in x 24-in plastic white tile with 12-in hole for exhaust air self-supported duct.LA146373-8280
9Ceiling Tile, 12-in hole, metal24-in x 24-in sheet metal tile with 12-in hole and built-in flange for exhaust air flexible duct kit.484490-1030
10Exhaust DiffuserDiverts exhaust air away from intake air, used for low profile ceilings or industrial areas.
Exhaust diffuser cannot be used for Condenser installation inside the rack.
484009-1610
11Exhaust Flange KitFlange to duct exhaust air away from Condenser. Includes 12-in. duct clamp.484009-1600

Other Accessories

NO.PART NAMEDESCRIPTIONPART NUMBER
12Connection Cable - ExtensionWire Harness A - Power is used when the EdgeCool Condenser unit is installed remotely from rack (> 9 ft. from Evaporator unit). Cable length: 10 ft.481950-4100
13Connection Cable - ExtensionWire Harness B - Signal is used when the EdgeCool Condenser unit is installed remotely from the rack (> 9 ft. from Evaporator unit). Cable length: 10 ft.481950-4110
14InsulationFor server rack insulation/condensation prevention and to improve airflow within the rack.484009-1620
15Pump Adaptor KitAttaches condensate pump (NOT included) to Evaporator unit. Includes bracket and electrical connector.484009-1640